Deutsch English
device: TR400 TR600 with analog output TR600 with RS485

sensor inputs:
sensor 1 sensor 2 sensor 3 sensor 4 sensor 5 sensor 6
input

switching points: [°C] [K] [s] [s]
sensor limits hysteresis t Alarm t Alarm off autoreset alarm-function
alarm 1 on off
alarm 2 on off
alarm 3 on off
alarm 4 on off
alarm 5 on off
alarm 6 on off

relay sensor alarm: closed-current mode operating current mode code-lock: on off

analog outputs: [°C] [°C]
sensor zero full-scale output
analog output 1 0..20 mA / 0..10 V 4..20 mA / 2..10 V
analog output 2 0..20 mA / 0..10 V 4..20 mA / 2..10 V

interface RS485:

protocol address baud rate parity stop bits *)
*) from firmware 12360-1400-04

comment: (max. 1027 characters). Deposed in TR as an element of configuration-file.

Download the created configuration-file to local computer. Load a configuration-file for editing All parameters on input screen are set to default


With the help of this input screen ZIEHL TR400 / TR600 (executions with USB connection) can be programmed easily

Download from input screen to USB flash drive and upload to TR400 / TR600
Create the required configuration on this input screen and download it with button "download" to your computer. For storage we recommend to give the file a meaningful name or store each original file separately it in a folder with an according name.
Before loading up to TR400 / TR600, this means normally before copying to USB flash drive, the file has to be named "TR600.cfg" (also at TR400 the name is TR600.cfg). Only files with this name (without index) are recognized from TR. Copy the file (TR600.cfg) in the root directory (top level) of the USB flash drive (file system FAT or FAT32). Stick the USB flash drive into TR400 / TR600 (ATTENTION: observe operating manual), Select Mode A at TR400 / TR600 and select alarm 2 with button alarm select (display Cnf to tr). Start upload of configuration file to TR with Set. A successful upload will be confirmed with OK in the digital display. At an error Err is displayed.
Remove USB flash drive from TR400 / TR600

Download from TR400 / TR600 to USB flash drive
Stick the USB flash drive (file system FAT or FAT32) into TR400 / TR600 (ATTENTION: observe operating manual), Select Mode A at TR400 / TR600 and select alarm 3 with button alarm select (display Cnf to USb). Start download of configuration to USB flash drive with Set. A successful download will be confirmed with OK in the digital display. At an error Err is displayed.
Remove USB flash drive from TR400 / TR600
On the USB flash drive a file TR600.cfg (also at TR400 the name is TR600.cfg) and a second file TR600_00.cfg are created. If more files are downloaded to the USB flash drive, TR600.cfg will be replaced by the actual file and additional files TR600_01.cfg, _02, ... are created.

Upload from USB flash drive to input screen
Stick USB flash drive in an input of the computer. Click browse and select the configuration file (TR600.cfg) on the USB flash drive. Click button Upload to transfer the file to the server. The data are now displayed on the input screen.The data can now be changed. Storing of configuration file see "download from TR400 / TR600 to USB flash drive".

Download operating manual TR400 / TR600

Version 12360-1402-03 -- 15.05.2018 /Sc